Room properties

The right pane shows the selected room's summary, then three sections you can fold: Room, Ventilation & loads and Walls. Values sit in locked, readable boxes until you press Edit; Edit unlocks every field.

A selected room and its properties

A folded section stays folded as you move from room to room, for as long as the app stays open. Walls open again for every room you select. Fold all on the Walls heading folds every wall at once and becomes Open all; it turns back into Fold all as soon as any wall is open.

Summary

Three lines sit above the sections.

The Room properties panel

Name

The room's name, bold, wrapping to at most two lines and then "…" if it still does not fit; hover it to read the full name. A new room is named in order, Room 001, Room 002 and so on. While editing, this line becomes a text box — its start, not its middle, is what shows for a name too long to fit. The ▾ beside it lists every piece of drawing text inside the room, exactly as written; pick one to put it in the box, then edit it as you like. A room with no text inside it shows a greyed-out No text inside this room.

Space type, Air-conditioned and Zone

The second line reads space type · Air-conditioned or Not air-conditioned · the room's zone, with the zone's colour swatch in front. These three are also editable in the Room section below.

Area, perimeter and glass

The third line reads floor area · perimeter · total glass area, each in the current Area or Length unit; hover it for the room's Width × Depth. These four figures show "—" until the room has a valid boundary. Width and depth are the drawing label's stated size when there is one, otherwise the shorter and longer sides of the smallest rectangle that encloses the outline. Total glass is the combined window area on the room's exterior walls. None of the three lines is itself editable; they update as soon as a field below changes or the boundary is redrawn.

Room

The Room section

The space type picker

Field What it does Default Read more
Room no. A number or code shown before the name. Blank Room number
Space type What the room is used for; sets the automatic occupancy, ventilation and load rates. Office Space Space type
Air-conditioned Whether the room is mechanically cooled. From the name Air-conditioned
Occupants How many people the room is sized for, and where that number comes from. From the label or density Occupants
Zone The unit the room belongs to. Zone 1 Zone
Schedule The hourly people, lighting and equipment profile the room follows. Always 100% Schedule
Ceiling Floor-to-ceiling height of this room. The floor's Ceiling Height Ceiling height

Room number

Room number is never read from the drawing — it is typed by hand.

Space type

A button showing the room's space type: click it to open the picker Choose a space type, choose, and press Use this space type (or double-click the type). The list is grouped by source, like the schedule picker: Industry standard holds the types of the standard outdoor-air table under its 11 categories in standard order — Correctional Facilities, Educational Facilities, Food and Beverage Service, General, Motels, Resorts, Dormitories, Office Buildings, Miscellaneous Spaces, Public Assembly Spaces, Residential, Retail, Sport and Entertainment — and App-specific holds the two types the app adds, Server Room and Toilet. Type in the search box to narrow the list by type or category name. The right side spells out the highlighted type's default occupancy, outdoor air per person and per floor area, and the sensible and latent heat per person, so you can check it before choosing. It also shows the lighting and equipment figures, marked as app defaults: today they are the same for every space type. Hovering a type, or the Space type button, shows its full name, for example "Industry standard · Office Buildings · Office Space".

Picking a space type re-derives the room's occupant density and every ventilation and load rate still set to Auto. The default is Office Space.

Air-conditioned

Yes or No. Filled in from the room's name: a name containing toilet, WC, washroom, wash room, restroom, rest room, bathroom, bath room, ladies, gents, shaft, electrical, elec room, fire stair, stair, lift lobby, riser, duct or pipe shaft starts as No. The grey note beside the box says from name while that is so, and the box follows every rename. Pick a value yourself and the note reads set by you; from then on renaming the room changes nothing.

A room set to No has no load of its own and is flagged NON-AC in the results. It still matters to its neighbours: a wall between it and an air-conditioned room carries a partition load on the other room's side. See Other side.

Occupants

Occupants runs from 0 to 999,999. Beside it, a source list reads where the number comes from:

"Where this number comes from: Label (stated in the drawing), Density (estimated from area and space type), or Manual (typed). Label is available only when the drawing states a capacity for this room."

Label is greyed out when the drawing states no capacity for this room. Typing a number switches the source to Manual on its own. See how occupants feed the load calculation.

Zone

The zones of the project, each with its own colour on the drawing. A new room is in the starting zone. A zone that cannot take this room, because it is a Single floor zone on another floor, is greyed out with the reason. The last entry, Edit zones…, opens Project config on Zones without changing the room. Zones are covered under Zones.

Schedule

The hourly people, lighting and equipment profile the room follows; Always 100% until one is assigned. The field is a button showing the schedule's short name: click it to open the picker Choose a schedule, choose, and press Use this schedule. The picker's footer can also make a schedule for this room on the spot: New custom… adds a blank Custom schedule and Duplicate and edit… adds an editable copy of the highlighted ECSBC schedule; each gives the room the new schedule and opens Project config on it. Edit in Project config… opens the highlighted Custom schedule there and leaves the room as it was. The field follows the same editing rule as Zone and is written on Save. Hovering the button, or a schedule in the picker, shows its full name with its source, for example "ECSBC 2024 · Office, daytime · Office". See Schedules.

Ceiling height

Shown as Ceiling on the panel, in the Length unit. Runs from 0.01 to 1000, and starts from the floor's Ceiling Height.

Ventilation & loads

The Ventilation and loads section

Field What it does Default Read more
Per person Outdoor air supplied per occupant. Auto Ventilation per person
Per area Outdoor air supplied per unit floor area. Auto Ventilation per area
LEED Extra outdoor air for a room that earns LEED credit. Off LEED extra fresh air
Lighting Heat gain from lighting per unit floor area. Auto Lighting load
Equipment Heat gain from equipment per unit floor area. Auto Equipment load
Infiltration Outdoor air leaking into the room, as air changes per hour. Blank Infiltration
Min airflow The least supply air the room may get, in ACH, per unit floor area, or as an airflow. Blank Min airflow

Each row (except Infiltration and Min airflow) shows its number, its unit, and a small Auto or Manual tag. Typing a value switches the tag to Manual on its own; while editing, a Manual value shows a ↺ button beside the tag, and clicking it discards the typed value and returns the field to Auto. The tag carries this tooltip:

"Auto: calculated from the room's space type. Manual: the value you typed, which nothing recalculates. Typing in the box switches this to Manual on its own."

Ventilation per person

Shown as Per person, in L/s·person (or the equivalent under the Units setting). Auto and Manual behave as described above: Auto is calculated from the room's space type; Manual freezes whatever is showing.

Ventilation per area

Shown as Per area, in L/s·m². Auto and Manual behave the same way as Ventilation per person.

LEED extra fresh air

Shown as LEED, a tick box that reads Extra fresh air (+30 %); the percentage is the project's, set under LEED air in Defaults. Tick it for a room that earns LEED credit and its outdoor air rises by that percentage, on top of the Per person and Per area rates you see above. The industry-standard minimum is not lost: the room's Ventilation cards in Explain still show it, the LEED share and the total used. A new room starts ticked while the project's Apply to all rooms is ticked. Ticked rooms carry a small LEED tag in the room list. A room set to not air-conditioned gets no extra air even if it is ticked.

Lighting load

Shown as Lighting, in W/m². Auto and Manual behave the same way as Ventilation per person.

Equipment load

Shown as Equipment, in W/m². Auto and Manual behave the same way as Ventilation per person.

Infiltration

Shown in ACH, air changes per hour: how many times in an hour the room's whole volume of air is replaced by outdoor air leaking in through the fabric, around openings and through door traffic. The unit is the same under every Units setting. Infiltration has no Auto and no tag — the field runs from 0 to 10 in steps of 0.25 and starts blank, with the tooltip:

"Outdoor air leaking into the room, as room-volumes per hour. Leave blank for none. Typical: 0.5 for a sealed office, 1 to 2 for a room with an outside door."

There is no standard table behind it: a blank field means no infiltration is counted, and nothing is assumed in its place. A typed figure is charged in full, whether or not the room's fresh air outweighs the leakage, so leave the field blank for a room whose fresh-air supply pressurises it. The leaked air is a room load, counted in Room Sens and Room Lat rather than with the fresh air; see What happens next for the formula.

Min airflow

The least supply air this room may get, typed as a number beside a dropdown that is both its basis and its unit: ACH, air changes per hour of the room's volume; airflow per unit floor area in the Airflow unit of the Units setting (L/s·m² or CFM/ft²); or a straight airflow in that unit (L/s or CFM). Like Infiltration it has no Auto and no tag, starts blank, and blank means no minimum. The tooltip:

"The least supply air this room may get. Leave blank for none. When the coil would need less, the supply air is raised to this and the Load config says how the extra air is handled."

Switching the dropdown keeps the number you typed and changes what it means, so 2 ACH becomes 2 of the per-area unit; retype the value after a switch. The per-area value is stored in CFM/ft² and the straight airflow in L/s, both converted for display as the density rows are.

When the coil selection's own Supply air comes out below this minimum, the minimum wins: the room's Supply air is raised to it and the room is flagged MIN AIRFLOW. What the coil does with the extra air is a Load config choice, see Min airflow.

Walls

The Walls section

Field What it does Default Read more
Exterior wall Whether the wall faces outdoors. As classified Exterior wall
Exterior How much of the wall faces outdoors, and from which end. As classified Exterior length
Ext. type Which construction preset the exterior part of the wall uses. The building's Exterior default Exterior wall type
Int. type Which construction preset the interior part of the wall uses. The building's Interior default Interior wall type
Other side What is behind the interior face of the wall. Follows neighbours Other side
Window A window on this wall. — Window cards

One foldable row appears per wall, in order around the room, titled with its number, direction, exposure and length — for example "Wall 1 · S · exterior · 4.00 m". A caption under the Walls heading, "U-values in …", says the unit once for every U-value shown inside; see Walls and windows for what each field means.

Edit, Redraw, Delete, Save, Cancel

Edit, Redraw and Delete show while the room is read-only; Save and Cancel replace them once editing begins. All five are described on Drawing and editing a room.

Reviewed and not reviewed

Reviewed means you have confirmed the room's properties are correct — all of them, not just its space type.

There is one way to say so: the ✓ Reviewed button at the foot of this panel, which appears only while the room still needs it. Press it when you have read the room and agree with every value. It needs no Edit first, alters nothing, and leaves you nothing to save.

Saving an edit does not mark a room reviewed. A room that was not reviewed stays that way after Save until you press ✓ Reviewed, and a room that was already reviewed stays reviewed when you edit and save it.

Until a room is reviewed, its row in the Rooms list shows in italics with a star, and hovering it adds "properties not reviewed" to the tooltip; Unreviewed first sorting brings such rooms to the top of the list.

Only Update Floor takes the mark away, from a room whose outline or contents the revised drawing changed. It has nothing to do with the flags on the results table.